Electrical installation
Use 0.5 … 2.5 mm
2
(20 … 14 AWG) cable with a sufficient voltage rating.
If you connect an inductive load (relay or contactor coil, motor) protect the relay
contacts with a varistor, RC filter (AC) or diode (DC). Install the protective
component as close to the inductive load as possible. Do not install protective
components at the relay output terminals.
DescriptionIdentification
Relay outputs RO4…RO7:4X103
Max. switching voltage: 250 V AC / 30 V DC
CommonCOM1
Max. switching current: 2 A
Normally closedNC2
Galvanically isolated.
Normally openNO3
5X104
CommonCOM1
Normally closedNC2
Normally openNO3
6X105
CommonCOM1
Normally closedNC2
Normally openNO3
7X106
CommonCOM1
Normally closedNC2
Normally openNO3
■
Start-up
To configure the operation of the relays added with the BREL-01 module:
1. Power up the drive.
2. Set the parameter
15.01 Extension module type
to 5 (BREL).
3. Use the control panel on the drive and set the parameters for relay outputs
RO4…RO7 in
15 I/O extension module
. Refer to the for parameter descriptions.
■
Configuration parameters
The configuration parameters of the BREL-01 module are in group
15 I/O extension
module
.
Def /
FbEq16/32
DescriptionName/ValueNo.
15 I/O extension module
Optional panel bus adapters and extension modules 229