Braking
time
1)
Refer-
ence
resistor
types
P
BRmax
P
BRcont
R
max
R
min
Type
ACS560
sDano-
therm
hpkWhpkWohmohm
Refer to
braking
resistor
manu-
fac-
turer’s
docu-
menta-
tion
3-phase UN = 380 or 480V
CBH
360 C T
406
210R
or
CAR
200 D T
406
210R
1.100.830.750.556289902A6-4
1.501.131.000.754289903A3-4
2.201.651.501.102859904A0-4
3.002.252.001.502069905A6-4
CBR-V
330 D T
406 78R
UL
4.403.302.002.201395307A2-4
6.004.503.003.001025309A4-4
8.006.005.004.00763212A6-4
CBR-V
560 D
HT 406
39R UL
11.008.257.505.505432017A-4
15.0011.2510.007.53923025A-4
CBT-H
560 D
HT 406
19R
20.121513.41103716033A-4
CBT-H
760 D
HT 406
16R
27.302017.8713.332710039A-4
CBT-H
760 D
HT 406
16R
34.02522.3516.672210046A-4
3AXD10000561047.xls B
The maximum permitted braking cycle of the braking resistor differs from
the that of the drive.
1)
The maximum braking capacity of the drive 1/10min (P
BRcont
* 150%), must
exceed the desired braking power.
P
BRmax
The maximum braking capacity of the drive, must exceed the desired braking
power.
P
BRcont
The maximum resistance value that can provide P
BRcont
. The resistance of
the brake resistor can be smaller if the application allows it.
R
max
Minimum allowed brake resistor that can be connected to the brake chopperR
min
Resistor braking 183