3. Connect the motor cable as follows:
Ground the shield 360° by tightening the clamp of the power cable grounding
shelf onto the stripped part of the cable (3a).
Connect the twisted shield of the cable to the grounding terminal (3b).
Connect the phase conductors of the cable to the terminals of T1/U, T2/V and
T3/W.
3a
3b
3c
Tighten the screws to the torque given below.
R2R0…R1Frame size
lbf·ftN·mlbf·ftN·m
0.9…1.11.2…1.50.40.5…0.6T1/U. T2/V. T3/W