Parameters 187
In1P Start; In2 Stop The sources of the start and stop commands are selected by
parameters 20.03 Ext1 in1 source and 20.04 Ext1 in2 source.
The state transitions of the source bits are interpreted as
follows:
Notes:
• Parameter 20.02 Ext1 start trigger type has no effect with
this setting.
• When source 2 is 0, the Start and Stop keys on the control
panel are disabled.
4
In1P Start; In2 Stop;
In3 Dir
The sources of the start and stop commands are selected by
parameters 20.03 Ext1 in1 source and 20.04 Ext1 in2 source.
The source selected by 20.05 Ext1 in3 source determines the
direction. The state transitions of the source bits are
interpreted as follows:
Notes:
• Parameter 20.02 Ext1 start trigger type has no effect with
this setting.
• When source 2 is 0, the Start and Stop keys on the control
panel are disabled.
5
In1P Start fwd; In2P
Start rev; In3 Stop
The sources of the start and stop commands are selected by
parameters 20.03 Ext1 in1 source, 20.04 Ext1 in2 source and
20.05 Ext1 in3 source. The source selected by 20.05 Ext1 in3
source determines the stop. The state transitions of the
source bits are interpreted as follows:
Note: Parameter 20.02 Ext1 start trigger type has no effect
with this setting.
6
Reserved 7…10
Control panel The start and stop commands are taken from the control
panel (or PC connected to the panel connector).
11
Fieldbus A The start and stop commands are taken from fieldbus adapter
A.
Note: Set also 20.02 Ext1 start trigger type to Level.
12
Reserved 13
No. Name/Value Description Def/FbEq16
State of source 1
(20.03)
State of source 2
(20.04)
Command
0
-
> 1 1 Start
Any 0 Stop
State of
source 1
(20.03)
State of
source 2
(20.04)
State of
source 3
(20.05)
Command
0
-
> 1 1 0 Start forward
0
-
> 1 1 1 Start reverse
Any 0 Any Stop
State of
source 1
(20.03)
State of
source 2
(20.04)
State of
source 3
(20.05)
Command
0
-
> 1 Any 1 Start forward
Any 0
-
> 1 1 Start reverse
Any Any 0 Stop