Parameters 171
Freq ref used 28.02 Frequency ref ramp output (page 226). 14
Reserved 15
Process PID out 40.01 Process PID output actual (page 278). 16
Reserved 17…19
Temp sensor 1
excitation
The output is used to feed an excitation current to the
temperature sensor 1, see parameter 35.11 Temperature 1
source. See also section Motor thermal protection (page
127).
20
Temp sensor 2
excitation
The output is used to feed an excitation current to the
temperature sensor 2, see parameter 35.21 Temperature 2
source. See also section Motor thermal protection (page
127).
21
Reserved 21…25
Abs motor speed
used
01.61 Abs motor speed used (page 149). 26
Abs motor speed % 01.62 Abs motor speed % (page 149). 27
Abs output
frequency
01.63 Abs output frequency (page 149). 28
Reserved 29
Abs motor torque 01.64 Abs motor torque (page 149). 30
Abs output power 01.65 Abs output power (page 149). 31
Abs motor shaft
power
01.68 Abs motor shaft power (page 149). 32
External PID1 out 71.01 External PID act value ((page
315). 33
Reserved 34…36
AO1 data storage 13.91 AO1 data storage (page 176). 37
AO2 data storage 13.92 AO2 data storage (page 176). 38
Other Source selection (see Terms and abbreviations on page 144). -
13.13 AO1 forced value Forced value that can be used instead of the selected output
signal. See parameter 13.02 AO force selection.
0.000 mA
0.000…22.000 mA /
0.000…11.000 V
Forced value for AO1. 1 = 1 unit
13.15 AO1 unit selection Selects the unit for readings and settings related to analog
input AO1.
Note:
In firmware ASCL2 and ASCL4), this setting must
match the corresponding hardware setting on the drive
control unit. See chapter Electrical installation, section
Switches in the Hardware manual of the drive and the default
control connections for the macro in use in chapter Control
macros (page 59). Control board reboot (either by cycling the
power or through parameter 96.08 Control board boot) is
required to validate any changes in the hardware settings.
mA
VVolts. 2
mA Milliamperes. 10
No. Name/Value Description Def/FbEq16
ACS580 FW.book Page 171 Wednesday, September 21, 2016 9:48 PM