80 
Parameter default values for different macros
96.04 Macro select 1 = 
ABB standard
17 = 
ABB stan-
dard (vector)
11 = 
3-wire
12 = 
Alternate
1
3 = 
Motor potenti-
ometer
10.24 RO1 source 2=Ready run 2=Ready run 2=Ready run 2=Ready run 2=Ready run
10.27 RO2 source 7=Running 7=Running 7=Running 7=Running 7=Running
10.30 RO3 source 15 = Fault (-1) 15 = Fault (-1) 15 = Fault (-1) 15 = Fault (-1) 15 = Fault (-1)
12.20 AI1 scaled at AI1 
max
50.0 1500.0 50.0 50.0 50.0
13.12 AO1 source 2 = Output 
frequency
1 = Motor 
speed used
2 = Output 
frequency
2 = Output 
frequency
2 = Output 
frequency
13.18 AO1 source max 50.0 1500.0 50.0 50.0 50.0
19.11 Ext1/Ext2 
selection
0 = EXT1 0 = EXT1 0 = EXT1 0 = EXT1 0 = EXT1
20.01 Ext1 commands 2 = In1 Start; 
In2 Dir
2 = In1 Start; 
In2 Dir
5 = In1P Start; 
In2 Stop; In3 
3 = In1 Start 
fwd; In2 Start 
1 = In1 Start
20.03 Ext1 in1 source 2 = DI1 2 = DI1 2 = DI1 2 = DI1 0 = Not 
selected
20.04 Ext1 in2 source 3 = DI2 0 = Not 
selected
3 = DI2 3 = DI2 3 = DI2
20.05 Ext1 in3 source 0 = Not 
selected
0 = Not 
selected
4 = DI3 0 = Not 
selected
0 = Not 
selected
20.06 Ext2 commands 0 = Not 
selected
0 = Not 
selected
0 = Not 
selected
0 = Not 
selected
0 = Not 
selected
20.08 Ext2 in1 source 0 = Not 
selected
0 = Not 
selected
0 = Not 
selected
0 = Not 
selected
0 = Not 
selected
20.09 Ext2 in2 source 0 = Not 
selected
0 = Not 
selected
0 = Not 
selected
0 = Not 
selected
0 = Not 
selected
20.12 Run enable 1 
source
1 =  Selected 1 =  Selected 1 = Selected 7 = DI6 7 = DI6
22.11 Ext1 speed ref1 1 = AI1 scaled 1 = AI1 scaled 1 = AI1 scaled 1 = AI1 scaled 15 = Motor 
potentiometer
22.18 Ext2 speed ref1 0 = Zero 0 = Zero 0 = Zero
0 = Zero 0 = Zero
22.22 Constant speed 
sel1
4 = DI3 4 = DI3 5 = DI4 4 = DI3 6 = DI5
22.23 Constant speed 
sel2
5 = DI4 5 = DI4 6 = DI5 5 = DI4 0 = Not 
selected
Chapter Parameters on page 143 shows the default values of all parameters for the 
ABB standard macro (factory macro). Some parameters have different default values 
for other macros. The tables below lists the default values for those parameter for 
each macro.