44 Settings, I/O and diagnostics on the control panel
Start, stop, reference
Use the Start, stop, reference submenu to set up start/stop commands, reference,
and related features, such as constant speeds or run permissions.
The table below provides detailed information about the available setting items in the
Start, stop, reference menu.
Menu item Description Corresponding
parameter
Reference from Sets where the drive gets its reference when
remote control (Ext1) is active.
28.11 Ext1 frequency
ref1 or
22.11 Ext1 speed ref1
12.19 AI1 scaled at AI1
min
Reference-related
settings (e.g. AI
scaling, AI2 scaling,
Motor potentiometer
settings) depending
on the selected
reference
The voltage or current fed to the input is converted
into a value the drive can use (e.g. reference).
12.20 AI1 scaled at AI1
max
Start/stop/dir from: Sets where the drive gets start, stop, and
(optionally) direction commands when remote
control (Ext1) is active.
20.01 Ext1 commands
Secondary control
location
Settings for the secondary remote control location,
Ext2. These settings include reference source,
start, stop, direction and command sources for
Ext2.
By default, Ext2 is set to Off.
19.11 Ext1/Ext2
selection
28.15 Ext2 frequency
ref1 or
22.18 Ext2 speed ref1
12.17 AI1 min
12.18 AI1 max
12.27 AI2 min
12.28 AI2 max
20.06 Ext2 commands
20.08 Ext2 in1 source
20.09 Ext2 in2 source
20.10 Ext2 in3 source
ACS580 FW.book Page 44 Wednesday, September 21, 2016 9:48 PM