28.11 Ext1 frequency ref1 Selects Ext1 frequency reference source 1.
Two signal sources can be defined by this parameter and
28.12 Ext1 frequency ref2. A mathematical function (28.13
Ext1 frequency function) applied to the two signals creates an
Ext1 reference (A in the figure below).
A digital source selected by 19.11 Ext1/Ext2 selection can be
used to switch between Ext1 reference and the
corresponding Ext2 reference defined by parameters 28.15
Ext2 frequency ref1, 28.16 Ext2 frequency ref2 and 28.17
Ext2 frequency function (B in the figure below).
AI1 scaled
Zero None. 0
AI1 scaled 12.12 AI1 scaled value (see page 167). 1
AI2 scaled 12.22 AI2 scaled value (see page 168). 2
Reserved 3
FB A ref1 03.05 FB A reference 1 (see page 150). 4
FB A ref2 03.06 FB A reference 2 (see page 150). 5
Reserved 6…7
EFB ref1 03.09 EFB reference 1 (see page 150). 8
EFB ref2 03.10 EFB reference 2 (see page 150). 9
Reserved 10…14
No. Name/Value Description Def/FbEq16
19.11
1
0
28.13
MUL
SUB
ADD
MIN
MAX
28.11
28.12
28.92
0
AI
FB
Other
0
AI
FB
Other
Ref1
28.17
MUL
SUB
ADD
MIN
MAX
28.15
28.16
0
AI
FB
Other
0
AI
FB
Other
Ref1
A
B
Ext1
Ext2
ACS580 FW.book Page 227 Wednesday, September 21, 2016 9:48 PM