236 Parameters
28.92 Frequency ref act 3 Displays the frequency reference after the function applied by
parameter 28.13 Ext1 frequency function (if any), and after
selection (19.11 Ext1/Ext2 selection). See the control chain
diagram on page 452.
This parameter is read-only.
-
-500.00…500.00
Hz
Frequency reference after selection. See par.
46.02
28.96 Frequency ref act 7 Displays the frequency reference after application of constant
frequencies, control panel reference, etc. See the control
chain diagram on page 452.
This parameter is read-only.
-
-500.00…500.00
Hz
Frequency reference 7. See par.
46.02
28.97 Frequency ref
unlimited
Displays the frequency reference after application of critical
frequencies, but before ramping and limiting. See the control
chain diagram on page 443.
This parameter is read-only.
-
-500.00…500.00
Hz
Frequency reference before ramping and limiting. See par.
46.02
30
30 Limits
Drive operation limits.
30.01 Limit word 1 Displays limit word 1.
This parameter is read-only.f
-
0000h…FFFFh Limit word 1. 1 = 1
No. Name/Value Description Def/FbEq16
Bit Name Description
0 Torq lim 1 = Drive torque is being limited by the motor control (undervoltage
control, current control, load angle control or pull-out control), or by the
torque limits defined by parameters.
1…2 Reserved
3 Torq ref max 1 = Torque reference is being limited by 26.09 Maximum torque ref or
30.20 Maximum torque 1
4 Torq ref min 1 = Torque reference is being limited by 26.08 Minimum torque ref or
30.19 Minimum torque 1
5 Tlim max speed 1 = Torque reference is being limited by the rush control because of
maximum speed limit (30.12 Maximum speed)
6 Tlim min speed 1 = Torque reference is being limited by the rush control because of
minimum speed limit (30.11 Minimum speed)
7 Max speed ref lim 1 = Speed reference is being limited by 30.12 Maximum speed
8 Min speed ref lim 1 = Speed reference is being limited by 30.11 Minimum speed
9 Max freq ref lim 1 = Frequency reference is being limited by 30.14 Maximum frequency
10 Min freq ref lim 1 = Frequency reference is being limited by 30.13 Minimum frequency
11…15 Reserved