438   Fieldbus control through a fieldbus adapter
 Parameter setting example: FPBA (PROFIBUS DP)
This example shows how to configure a basic speed control application that uses the 
PROFIdrive communication profile with PPO Type 2. The start/stop commands and 
reference are according to the PROFIdrive profile, speed control mode.
The reference values sent over the fieldbus have to be scaled within the drive so they 
have the desired effect. The reference value ±16384 (4000h) corresponds to the 
range of speed set in parameter 46.01 Speed scaling (both forward and reverse 
directions). For example, if 46.01 is set to 480 rpm, then 4000h sent over fieldbus will 
request 480 rpm.
The table below gives the recommended drive parameter settings. 
Direction PZD1 PZD2 PZD3 PZD4 PZD5 PZD6
Out Control word Speed reference Acc time 1 Dec time 1
In Status word Speed actual value Motor current DC voltage
Drive parameter Setting for ACX580 
drives
Description
50.01 FBA A enable 1 = [slot number] s communication between the drive and 
the fieldbus adapter module.
50.04 FBA A ref1 type 4 = Speed Selects the fieldbus A reference 1 type 
and scaling.
50.07 FBA A actual 1 type 0 = Speed or 
frequency
Selects the actual value type and scaling 
according to the currently active Ref1 
mode defined in parameter 50.04.
51.01 FBA A type 1 = FPBA
1)
Displays the type of the fieldbus adapter 
module.
51.02 Node address 3
2)
Defines the PROFIBUS node address of 
the fieldbus adapter module.
51.03 Baud rate 12000
1)
Displays the current baud rate on the 
PROFIBUS network in kbit/s.
51.04 MSG type 1 = PPO2
1)
Displays the telegram type selected by 
the PLC configuration tool.
51.05 Profile 0 = PROFIdrive Selects the Control word according to the 
PROFIdrive profile (speed control mode).
51.07 RPBA mode 0 = Disabled Disables the RPBA emulation mode.
52.01 FBA data in1 4 = SW 16bit
1)
Status word
52.02 FBA data in2 5 = Act1 16bit Actual value 1
52.03 FBA data in3 01.07
2)
Motor current
52.05 FBA data in5 01.11
2)
DC voltage
53.01 FBA data out1 1 = CW 16bit
1)
Control word
53.02 FBA data out2 2 = Ref1 16bit Reference 1 (speed)
53.03 FBA data out3 23.12
2)
Acceleration time 1
ACS580 FW.book  Page 438  Wednesday, September 21, 2016  9:48 PM