Fieldbus control through a fieldbus adapter 439
The start sequence for the parameter example above is given below.
Control word:
477h (1143 decimal) –> READY TO SWITCH ON
47Fh (1151 decimal) –> OPERATING (Speed mode)
53.05 FBA data out5 23.13
2)
Deceleration time 1
51.27 FBA A par refresh 1 = Configure Validates the configuration parameter
settings.
19.12 Ext1 control mode 2 = Speed Selects speed control as the control
mode 1 for external control location
EXT1.
20.01 Ext1 commands 12 = Fieldbus A Selects fieldbus adapter A as the source
of the start and stop commands for
external control location EXT1.
20.02 Ext1 start trigger type 1 = Level Selects a level-triggered start signal for
external control location EXT1.
22.11 Ext1 speed ref1 4 = FB A ref1 Selects fieldbus A reference 1 as the
source for speed reference 1.
1)
Read-only or automatically detected/set
2)
Example
Drive parameter Setting for ACX580
drives
Description
ACS580 FW.book Page 439 Wednesday, September 21, 2016 9:48 PM