36 Load analyzer
Peak value and amplitude logger settings.
See also section Load analyzer (page 135).
36.01 PVL signal source Selects the signal to be monitored by the peak value logger.
The signal is filtered using the filtering time specified by
parameter 36.02 PVL filter time.
The peak value is stored, along with other pre-selected
signals at the time, into parameters 36.1036.15.
The peak value logger can be reset using parameter 36.09
Reset loggers. The logger is also reset whenever the signal
source is changed. The date and time of the last reset are
stored into parameters 36.16 and 36.17 respectively.
Output power
Not selected None (peak value logger disabled). 0
Motor speed used 01.01 Motor speed used (page 147). 1
Reserved 2
Output frequency 01.06 Output frequency (page 147). 3
Motor current 01.07 Motor current (page 147). 4
Reserved 5
Motor torque 01.10 Motor torque (page 147). 6
DC voltage 01.11 DC voltage (page 147). 7
Output power 01.14 Output power (page 148). 8
Reserved 9
Speed ref ramp in 23.01 Speed ref ramp input (page 212). 10
Speed ref ramp out 23.02 Speed ref ramp output (page 213). 11
Speed ref used 24.01 Used speed reference (page 217). 12
Torque ref used 26.02 Torque reference used (page
222). 13
Freq ref used 28.02 Frequency ref ramp output (page 226). 14
Reserved 15
Process PID out 40.01 Process PID output actual (page 278). 16
Other Source selection (see Terms and abbreviations on page 144). -
36.02 PVL filter time Peak value logger filtering time. See parameter 36.01 PVL
signal source.
2.00 s
0.00…120.00 s Peak value logger filtering time. 100 = 1 s
36.06 AL2 signal source Selects the signal to be monitored by amplitude logger 2. The
signal is sampled at 200 ms intervals.
The results are displayed by parameters 36.4036.49. Each
parameter represents an amplitude range, and shows what
portion of the samples fall within that range.
The signal value corresponding to 100% is defined by
parameter 36.07 AL2 signal scaling.
Amplitude logger 2 can be reset using parameter 36.09 Reset
loggers. The logger is also reset whenever the signal
source or scaling is changed. The date and time of the last
reset are stored into parameters 36.50 and 36.51
respectively.
For the selections, see parameter 36.01 PVL signal source.
Motor torque
36.07 AL2 signal scaling Defines the signal value that corresponds to 100% amplitude. 100.00
0.00…32767.00 Signal value corresponding to 100%. 1 = 1
No. Name/Value Description Def/FbEq16