Parameters 149
01.52 Current day kWh Current day energy consumption. This is the energy of the
last 24 hours (not necessarily continuous) the drive has been
running, not the energy of a calendar day. The value is set to
the value before the power cycle when the drive is again up
and running.
-
0.00… 1000000.00
kWh
Energy. 1 = 1 kWh
01.53 Previous day kWh Previous day energy consumption. The value 01.52 Current
day kWh is stored here when its value has been cumulated
for 24 hours. The value is set to the value before the power
cycle when the drive is again up and running.
-
0.00… 1000000.00
kWh
Energy. 1 = 1 kWh
01.61 Abs motor speed
used
Absolute value of parameter 01.01 Motor speed used.-
0.00… 30000.00
rpm
Estimated motor speed. See par.
46.01
01.62 Abs motor speed % Absolute value of parameter 01.03 Motor speed %.-
0.00… 1000.00% Estimated motor speed. 10 = 1%
01.63 Abs output
frequency
Absolute value of parameter 01.06 Output frequency.-
0.00…500.00 Hz Estimated output frequency. See par.
46.02
01.64 Abs motor torque Absolute value of parameter 01.10 Motor torque.-
0.0…1600.0% Motor torque. See par.
46.03
01.65 Abs output power Absolute value of parameter 01.14 Output power.-
0.00… 32767.00
kW or hp
Output power. 1 = 1 kW
01.66 Abs output
power % motor
nom
Absolute value of parameter 01.15 Output power % of motor
nom.
-
0.00… 300.00% Output power. 1 = 1%
01.67 Abs output
power % drive nom
Absolute value of parameter 01.16 Output power % of drive
nom.
-
0.00… 300.00% Output power. 1 = 1%
01.68 Abs motor shaft
power
Absolute value of parameter 01.17 Motor shaft power.-
0.00… 32767.00
kW or hp
Motor shaft power. 1 = 1 kW
03
03 Input references
Values of references received from various sources.
All parameters in this group are read-only unless otherwise
noted.
03.01 Panel reference Reference 1 given from the control panel or PC tool. -
-100000.00…
100000.0
0
Control panel or PC tool reference. 1 = 1
0
No. Name/Value Description Def/FbEq16