Program features 97
Settings
Menu - Primary settings - Ramps
Speed reference ramping: Parameters 23.1123.15 and 46.01
(pages 213 and 297).
Torque reference ramping: Parameters 01.30, 26.18 and 26.19
(pages 148 and 225).
Frequency reference ramping: Parameters 28.71… and 46.02
(pages 233 and 297).
Jogging: Parameters 23.20 and 23.21 (page 214).
Motor potentiometer: Parameter 22.75 (page 212).
Emergency stop (“Off3 mode): Parameter 23.23 Emergency stop time
(page 214).
Constant speeds/frequencies
Constant speeds and frequencies are predefined references that can be quickly
activated, for example, through digital inputs. It is possible to define up to 7 speeds
for speed control and 7 constant frequencies for frequency control.
WARNING: Speeds and frequencies override the normal reference
irrespective of where the reference is coming from.
Settings
Menu - Primary settings - Start, stop, reference - Constant frequencies,
Menu - Primary settings - Start, stop, reference - Constant speeds
Parameter groups 22 Speed reference selection (page 204) and 28 Frequency
reference chain (page 226).
Critical speeds/frequencies
Critical speeds (sometimes called “skip speeds”) can be predefined for applications
where it is necessary to avoid certain motor speeds or speed ranges because of, for
example, mechanical resonance problems.
The critical speeds function prevents the reference from dwelling within a critical band
for extended times. When a changing reference (22.87 Speed reference act 7) enters
a critical range, the output of the function (22.01 Speed ref unlimited) freezes until the
reference exits the range. Any instant change in the output is smoothed out by the
ramping function further in the reference chain.
When the drive is limiting the allowed output speeds/frequencies, it limits to the
absolutely lowest critical speed (critical speed low or critical frequency low) when
accelerating from standstill, unless the speed reference is over the upper critical
speed/ frequency limit.