226 Parameters
26.74 Torque ref ramp out Displays the torque reference after limiting and ramping. See
the control chain diagram on page 449.
This parameter is read-only.
-
-1600.0…1600.0% Torque reference after limiting and ramping. See par.
46.03
26.75 Torque reference
act 5
Displays the torque reference after control mode selection.
See the control chain diagram on page 451.
This parameter is read-only.
-
-1600.0…1600.0% Torque reference after control mode selection. See par.
46.03
28
28 Frequency reference
chain
Settings for the frequency reference chain.
See the control chain diagrams on pages 452 and 443.
28.01 Frequency ref ramp
input
Displays the used frequency reference before ramping. See
the control chain diagram on page 452.
This parameter is read-only.
-
-500.00…500.00
Hz
Frequency reference before ramping. See par.
46.02
28.02 Frequency ref ramp
output
Displays the final frequency reference (after selection,
limitation and ramping). See the control chain diagram on
page 452.
This parameter is read-only.
-
-500.00…500.00
Hz
Final frequency reference. See par.
46.02
No. Name/Value Description Def/FbEq16