278 Parameters
37.33 ULC overload point
3
Defines the third overload point.
See parameter 37.31 ULC overload point 1.
300.0%
-1600.01600.0% Overload point. 1 = 1%
37.34 ULC overload point
4
Defines the fourth overload point.
See parameter 37.31 ULC overload point 1.
300.0%
-1600.01600.0% Overload point. 1 = 1%
37.35 ULC overload point
5
Defines the fifth overload point.
See parameter 37.31 ULC overload point 1.
300.0%
-1600.01600.0% Overload point. 1 = 1%
37.41 ULC overload timer Defines the time period for which time the monitored signal
must remain continuously over the overload curve.
20.0 s
0.0…10000.0 s Time. 1 = 1 s
37.42 ULC underload
timer
Defines the time period for which time the monitored signal
must remain continuously below the underload curve.
20.0 s
0.0…10000.0 s Time. 1 = 1 s
40
40 Process PID set 1
Parameter values for process PID control.
The drive output can be controlled by the process PID. When
the process PID control is enabled, the drive controls the
process feedback to the reference value.
Two different parameter sets can be defined for the process
PID. One parameter set is in use at a time. The first set is
made up of parameters 40.0740.50, the second set is
defined by the parameters in group 41 Process PID set 2.
The binary source that defines which set is used is selected
by parameter 40.57 PID set1/set2 selection.
See also the control chain diagrams on pages 452 and 453.
To set the PID customer unit, select Menu - Primary settings
- PID - Unit on the panel.
40.01 Process PID output
actual
Displays the output of the process PID controller. See the
control chain diagram on page 453.
This parameter is read-only.
-
-32768.00…
32767.00 PID
customer units
Process PID controller output. 1 = 1 PID
customer unit
40.02 Process PID
feedback actual
Displays the value of process feedback after source
selection, mathematical function (parameter 40.10 Set 1
feedback function), and filtering. See the control chain
diagram on page 452.
This parameter is read-only.
-
-32768.00…
32767.00 PID
customer units
Process feedback. 1 = 1 PID
customer unit
40.03 Process PID
setpoint actual
Displays the value of process PID setpoint after source
selection, mathematical function (40.18 Set 1 setpoint
function), limitation and ramping. See the control chain
diagram on page 453.
This parameter is read-only.
-
-32768.00…
32767.00 PID
customer units
Setpoint for process PID controller. 1 = 1 PID
customer unit
No. Name/Value Description Def/FbEq16
ACS580 FW.book Page 278 Wednesday, September 21, 2016 9:48 PM