Parameters 287
40.49 Set 1 tracking mode Activates (or selects a source that activates) tracking mode.
In tracking mode, the value selected by parameter 40.50 Set
1 tracking ref selection is substituted for the PID controller
output. See also section Tracking (page 102).
1 = Tracking mode enabled
Not selected
Not selected 0. 0
Selected 1. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
Reserved 8…17
Timed function 1 Bit 0 of 34.01 Timed functions status (see page 255). 18
Timed function 2 Bit 1 of 34.01 Timed functions status (see page 255). 19
Timed function 3 Bit 2 of 34.01 Timed functions status (see page 255). 20
Supervision 1 Bit 0 of 32.01 Supervision status (see page 248). 21
Supervision 2 Bit 1 of 32.01 Supervision status (see page 248). 22
Supervision 3 Bit 2 of 32.01 Supervision status (see page 248). 23
Other [bit] Source selection (see Terms and abbreviations on page 144). -
40.50 Set 1 tracking ref
selection
Selects the value source for tracking mode. See parameter
40.49
Set 1 tracking mode.
Not selected
Not selected None. 0
AI1 scaled 12.12 AI1 scaled value (see page 167). 1
AI2 scaled 12.22 AI2 scaled value (see page 168). 2
FB A ref1 03.05 FB A reference 1 (see page 150). 3
FB A ref2 03.06 FB A reference 2 (see page 150). 4
Other Source selection (see Terms and abbreviations on page 144). -
40.57 PID set1/set2
selection
Selects the source that determines whether process PID
parameter set 1 (parameters 40.0740.50) or set 2 (group
41 Process PID set 2) is used.
PID set 1
PID set 1 0. Process PID parameter set 1 in use. 0
PID set 2 1. Process PID parameter set 2 in use. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
Reserved 8…17
Timed function 1 Bit 0 of 34.01 Timed functions status (see page 255). 18
Timed function 2 Bit 1 of 34.01 Timed functions status (see page 255). 19
No. Name/Value Description Def/FbEq16
ACS580 FW.book Page 287 Wednesday, September 21, 2016 9:48 PM