286 Parameters
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
Reserved 8…17
Timed function 1 Bit 0 of 34.01 Timed functions status (see page 255). 18
Timed function 2 Bit 1 of 34.01 Timed functions status (see page 255). 19
Timed function 3 Bit 2 of 34.01 Timed functions status (see page 255). 20
Supervision 1 Bit 0 of 32.01 Supervision status (see page 248). 21
Supervision 2 Bit 1 of 32.01 Supervision status (see page 248). 22
Supervision 3 Bit 2 of 32.01 Supervision status (see page 248). 23
Other [bit] Source selection (see Terms and abbreviations on page 144). -
40.43 Set 1 sleep level Defines the start limit for the sleep function. If the value is 0.0,
set 1 sleep mode is disabled.
The sleep function compares PID output (parameter 40.01
Process PID output actual) to the value of this parameter. If
PID output remains below this value longer than the sleep
delay defined by 40.44 Set 1 sleep delay, the drive enters the
sleep mode and stops the motor.
0.0
0.0…32767.0 Sleep start level. 1 = 1
40.44 Set 1 sleep delay Defines a delay before the sleep function actually becomes
enabled, to prevent nuisance sleeping.
The delay timer starts when the sleep mode is enabled by
parameter 40.43 Set 1 sleep level, and resets when the sleep
mode is disabled.
60.0 s
0.0…3600.0 s Sleep start delay. 1 = 1 s
40.45 Set 1 sleep boost
time
Defines a boost time for the sleep boost step. See parameter
40.46 Set 1 sleep boost step.
0.0 s
0.0…3600.0 s Sleep boost time. 1 = 1 s
40.46 Set 1 sleep boost
step
When the drive is entering sleep mode, the process setpoint
is increased by this value for the time defined by parameter
40.45 S
et 1 sleep boost time.
If active, sleep boost is aborted when the drive wakes up.
0.0 PID
customer
units
0.0…32767.0 PID
customer units
Sleep boost step. 1 = 1 PID
customer unit
40.47 Set 1 wake-up
deviation
Defines the wake-up level as deviation between process
setpoint and feedback.
When the deviation exceeds the value of this parameter, and
remains there for the duration of the wake-up delay (40.48
Set 1 wake-up delay), the drive wakes up.
See also parameter 40.31 Set 1 deviation inversion.
0.00 PID
customer
units
-32768.00…
32767.00 PID
customer units
Wake-up level (as deviation between process setpoint and
feedback).
1 = 1 PID
customer unit
40.48 Set 1 wake-up
delay
Defines a wake-up delay for the sleep function to prevent
nuisance wake-ups. See parameter 40.47 Set 1 wake-up
deviation.
The delay timer starts when the deviation exceeds the wake-
up level (40.47 Set 1 wake-up deviation), and resets if the
deviation falls below the wake-up level.
0.50 s
0.00…60.00 s Wake-up delay. 1 = 1 s
No. Name/Value Description Def/FbEq16