284 Parameters
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
Reserved 8…17
Timed function 1 Bit 0 of 34.01 Timed functions status (see page 255). 18
Timed function 2 Bit 1 of 34.01 Timed functions status (see page 255). 19
Timed function 3 Bit 2 of 34.01 Timed functions status (see page 255). 20
Supervision 1 Bit 0 of 32.01 Supervision status (see page 248). 21
Supervision 2 Bit 1 of 32.01 Supervision status (see page 248). 22
Supervision 3 Bit 2 of 32.01 Supervision status (see page 248). 23
Other [bit] Source selection (see Terms and abbreviations on page 144). -
40.31 Set 1 deviation
inversion
Inverts the input of the process PID controller.
0 = Deviation not inverted (Deviation = Setpoint - Feedback)
1 = Deviation inverted (Deviation = Feedback - Setpoint)
See also section Sleep and boost functions for process PID
control (page 101).
Not inverted
(Ref - Fbk)
Not inverted
(Ref - Fbk)
0. 0
Inverted (Fbk - Ref) 1. 1
Other [bit] Source selection (see Terms and abbreviations on page 144). -
40.32 Set 1 gain Defines the gain for the process PID controller. See
parameter
40.33 Set 1 integration time.
1.00
0.10…100.00 Gain for PID controller. 100 = 1
40.33 Set 1 integration
time
Defines the integration time for the process PID controller.
This time needs to be set to the same order of magnitude as
the reaction time of the process being controlled, otherwise
instability will result.
Note: Setting this value to 0 disables the “I” part, turning the
PID controller into a PD controller.
60.0 s
0.0…9999.0 s Integration time. 1 = 1 s
No. Name/Value Description Def/FbEq16
Ti
O
I
G × I
G × I
I = controller input (error)
O = controller output
G = gain
Ti = integration time
Time
Error/Controller output
ACS580 FW.book Page 284 Wednesday, September 21, 2016 9:48 PM