Settings, I/O and diagnostics on the control panel 49
Fieldbus
Use the settings in the Fieldbus submenu to use the drive with a fieldbus:
Modbus (RTU or TCP)
•PROFIBUS
PROFINET
Ethernet/IP Rev D: more
You can also configure all the fieldbus related settings via the parameters (parameter
groups 50 Fieldbus adapter (FBA), 51 FBA A settings, 52 FBA A data in, 53 FBA A
data out, 58 Embedded fieldbus), but the purpose of the Fieldbus menu is to make
the protocol configurations easier.
Note that only Modbus RTU is embedded and the other fieldbus modules are optional
adapters. For the optional modules, the following adapters are required to the needed
protocols:
ModbusTCP: FENA-11/-21
PROFIBUS: FBPA-01
PROFINET FENA-11/-21
Ethernet/IP: FENA-11/-21
The table below provides detailed information about the available setting items in the
Fieldbus menu. Note that some of the items only became active once you have d
fieldbus.
Menu item Description Corresponding
parameter
Fieldbus selection Select this if you want to use the drive with a
fieldbus.
51.01 FBA A type
58.01 Protocol
ACS580 FW.book Page 49 Wednesday, September 21, 2016 9:48 PM