164 Parameters
10.99 RO/DIO control
word
Storage parameter for controlling the relay outputs eg.
through the embedded fieldbus interface. To control the relay
outputs (RO) of the drive, send a control word with the bit
assignments shown below as Modbus I/O data. Set the target
selection parameter of that particular data (58.10158.114)
to RO/DIO control word. In the source selection parameter of
the desired output, select the appropriate bit of this word.
0000h
0000h…FFFFh RO
/DIO
control word. 1 = 1
10.101 RO1 toggle counter Displays the number of times relay output RO1 has changed
states.
-
0…4294967000 State change count. 1 = 1
10.102 RO2 toggle counter Displays the number of times relay output RO2 has changed
states.
-
0…4294967000 State change count. 1 = 1
10.103 RO3 toggle counter Displays the number of times relay output RO3 has changed
states.
-
0…4294967000 State change count. 1 = 1
11
11 Standard DIO, FI, FO
Configuration of the frequency input.
11.21 DI5 configuration (Only visible with firmware ASCD2 and ASCD4)
Selects how digital input 5 is used.
Digital input
Digital input DI5 is used as a digital input. 0
Frequency input DI5 is used as a frequency input. 1
11.25 DI6 configuration (Only visible with firmware ASCL2 and ASCL4)
Selects how digital input 6 is used.
Digital input
Digital input DI6 is used as a digital input. 0
Frequency input DI6 is used as a frequency input. 1
11.38 Freq in 1 actual
value
Displays the value of frequency input 1 (via DI6 when it is
used as a frequency input) before scaling. See parameter
11.42 Freq in 1 min.
This parameter is read-only.
-
0 16000 Hz Unscaled value of frequency input 1. 1 = 1 Hz
No. Name/Value Description Def/FbEq16
Bit Name Description
0 RO1 Source bits for relay outputs RO1…RO3. See parameters 10.24,
10.27 and 10.30
.
1RO2
2RO3
3 RO4 Source bits for relay outputs RO4…RO5 with a CHDI-01 or CMOD-01
extension module. See parameters 15.07 and.15.10.
4RO5
5 Reserved
6 DIO1 Source bit for digital outputs DO1 with a CMOD-01 extension module.
See parameter 15.23.
7…15 Reserved
ACS580 FW.book Page 164 Wednesday, September 21, 2016 9:48 PM