Settings, I/O and diagnostics on the control panel 51
Advanced functions
The Advanced functions submenu contains settings for advanced functions, such
as triggering or resetting faults via I/O, signal supervision, using the drive with timed
functions, or switching between several entire sets of settings.
The table below provides detailed information about the available setting items in the
Advanced functions menu.
Apply settings to
fieldbus module
Applies modified settings to the fieldbus module.
51.27 FBA A par refresh
58.06 Communication
control
Menu item Description Corresponding
parameter
External events s you to define custom faults or warnings you can
trigger via digital input. The texts of these
messages are customizable.
31.01 External event 1
source
31.02 External event 1
type
31.03 External event 2
source
31.04 External event 2
type
31.05 External event 3
source
31.06 External event 3
type
Additional fault reset You can reset an active fault via I/O: a rising pulse
in the selected input means reset.
A fault can be reset from the fieldbus even if Reset
faults manually is unselected.
31.11 Fault reset
selection
Reset from keypad
and...
Define from where you want to reset faults
manually. Note that this submenu is active only if
you have selected to reset faults manually.
31.11 Fault reset
selection
Autoreset faults Reset faults automatically. For more information,
see Automatic fault resets on page 133.
31.12 Autoreset
selection
31.14 Number of trials
31.15 Total trials time
31.16 Delay time
Menu item Description Corresponding
parameter
ACS580 FW.book Page 51 Wednesday, September 21, 2016 9:48 PM