Parameters 289
40.92 Setpoint data
storage
Storage parameter for receiving a process setpoint value eg.
through the embedded fieldbus interface.
The value can be sent to the drive as Modbus I/O data. Set
the target selection parameter of that particular data
(58.101…58.114)) to Setpoint data storage. In 40.16 Set 1
setpoint 1 source (or 40.17 Set 1 setpoint 2 source), select
Setpoint data storage.
-
-327.68…327.67 Storage parameter for process setpoint. 100 = 1
41
41 Process PID set 2
A second set of parameter values for process PID control.
The selection between this set and first set (parameter group
40 Process PID set 1) is made by parameter 40.57 PID
set1/set2 selection.
See also parameters 40.01…40.06, and the control chain
diagrams on pages 452 and 453.
41.08 Set 2 feedback 1
source
See parameter 40.08 Set 1 feedback 1 source. AI2 percent
41.09 Set 2 feedback 2
source
See parameter 40.09 Set 1 feedback 2 source. Not selected
41.10 Set 2 feedback
function
See parameter 40.10 Set 1 feedback function. In1
41.11 Set 2 feedback filter
time
See parameter 40.11 Set 1 feedback filter time. 0.000 s
41.16 Set 2 setpoint 1
source
See parameter 40.16 Set 1 setpoint 1 source. AI1 percent
41.17 Set 2 setpoint 2
source
See parameter 40.17 Set 1 setpoint 2 source. Not selected
41.18 Set 2 setpoint
function
See parameter 40.18 Set 1 setpoint function. In1
41.19 Set 2 internal
setpoint sel1
See parameter 40.19 Set 1 internal setpoint sel1. Not selected
41.20 Set 2 internal
setpoint sel2
See parameter 40.20 Set 1 internal setpoint sel2. Not selected
41.21 Set 2 internal
setpoint 1
See parameter 40.21 Set 1 internal setpoint 1. 0.00 PID
customer
units
41.22 Set 2 internal
setpoint 2
See parameter 40.22 Set 1 internal setpoint 2. 0.00 PID
customer
units
41.23 Set 2 internal
setpoint 3
See parameter 40.23 Set 1 internal setpoint 3. 0.00 PID
customer
units
41.26 Set 2 setpoint min See parameter 40.26
Set 1 setpoint min.0.00
41.27 Set 2 setpoint max See parameter 40.27 Set 1 setpoint max. 32767.00
41.28 Set 2 setpoint
increase time
See parameter 40.28 Set 1 setpoint increase time. 0.0 s
41.29 Set 2 setpoint
decrease time
See parameter 40.29 Set 1 setpoint decrease time. 0.0 s
41.30 Set 2 setpoint
freeze enable
See parameter 40.30 Set 1 setpoint freeze enable. Not selected
No. Name/Value Description Def/FbEq16
ACS580 FW.book Page 289 Wednesday, September 21, 2016 9:48 PM