282 Parameters
sqrt(In1-In2) Square root of (source 1 - source 2). 9
sqrt(In1+In2) Square root of (source 1 + source 2). 10
sqrt(In1)+sqrt(In2) Square root of source 1 + square root of source 2. 11
40.19 Set 1 internal
setpoint sel1
Selects together with 40.20 Set 1 internal setpoint sel2 the
internal setpoint out of the presets defined by parameters
40.2140.23.
Note: Parameters 40.16 Set 1 setpoint 1 source and 40.17
Set 1 setpoint 2 source must be set to Internal setpoint.
Not selected
Not selected 0. 0
Selected 1. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
Reserved 8…17
Timed function 1 Bit 0 of 34.01 Timed functions status (see page 255). 18
Timed function 2 Bit 1 of 34.01 Timed functions status (see page 255). 19
Timed function 3 Bit 2 of 34.01 Timed functions status (see page 255). 20
Supervision 1 Bit 0 of 32.01 Supervision status (see page 248). 21
Supervision 2 Bit 1 of 32.01 Supervision status (see page 248). 22
Supervision 3 Bit 2 of 32.01 Supervision status (see page 248
). 23
Other [bit] Source selection (see Terms and abbreviations on page 144). -
40.20 Set 1 internal
setpoint sel2
Selects together with 40.19 Set 1 internal setpoint sel1 the
internal setpoint used out of the three internal setpoints
defined by parameters 40.2140.23. See table at 40.19 Set
1 internal setpoint sel1.
Not selected
Not selected 0. 0
Selected 1. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
Reserved 8…17
No. Name/Value Description Def/FbEq16
Source defined
by par. 40.19
Source defined
by par. 40.20
Setpoint preset active
0 0 Setpoint source
1 0 1 (par. 40.21)
0 1 2 (par. 40.22)
1 1 3 (par. 40.23)
ACS580 FW.book Page 282 Wednesday, September 21, 2016 9:48 PM