280 Parameters
Other Source selection (see Terms and abbreviations on page 144). -
40.09 Set 1 feedback 2
source
Selects the second source of process feedback. The second
source is used only if the setpoint function requires two
inputs.
For the selections, see parameter 40.08 Set 1 feedback 1
source.
Not selected
40.10 Set 1 feedback
function
Defines how process feedback is calculated from the two
feedback sources selected by parameters 40.08 Set 1
feedback 1 source and 40.09 Set 1 feedback 2 source.
In1
In1 Source 1. 0
In1+In2 Sum of sources 1 and 2. 1
In1-In2 Source 2 subtracted from source 1. 2
In1*In2 Source 1 multiplied by source 2. 3
In1/In2 Source 1 divided by source 2. 4
MIN(In1,In2) Smaller of the two sources. 5
MAX(In1,In2) Greater of the two sources. 6
AVE(In1,In2) Average of the two sources. 7
sqrt(In1) Square root of source 1. 8
sqrt(In1-In2) Square root of (source 1 - source 2). 9
sqrt(In1+In2) Square root of (source 1 + source 2). 10
sqrt(In1)+sqrt(In2) Square root of source 1 + square root of source 2. 11
40.11 Set 1 feedback filter
time
Defines the filter time constant for process feedback. 0.000 s
0.000…30.000 s Feedback filter time. 1 = 1 s
40.16 Set 1 setpoint 1
source
Selects the primary source of process PID setpoint. See the
control chain diagram on page 452.
AI1 percent
Not selected None. 0
Reserved 1
Internal setpoint Internal setpoint. See parameter 40.19 Set 1 internal setpoint
sel1.
2
AI1 scaled 12.12 AI1 scaled value (see page 167). 3
AI2 scaled 12.22 AI2 scaled value (see page 168). 4
Reserved 5…7
Motor
potentiometer
22.80 Motor potentiometer ref act (output of the motor
potentiometer).
8
Reserved 9
Freq in scaled 11.39 Freq in 1 scaled value (see page 165). 10
AI1 percent 12.101 AI1 percent value (see page 170)11
AI2 percent 12.102 AI2 percent value (see page 170
)12
No. Name/Value Description Def/FbEq16