Parameters 301
47.22 Data storage 2
int16
Data storage parameter 18. 0
-32768…32767 16-bit data. 1 = 1
47.23 Data storage 3
int16
Data storage parameter 19. 0
-32768…32767 16-bit data. 1 = 1
47.24 Data storage 4
int16
Data storage parameter 20. 0
-32768…32767 16-bit data. 1 = 1
49
49 Panel port
communication
Communication settings for the control panel port on the
drive.
49.01 Node ID number Defines the node ID of the drive. All devices connected to the
network must have a unique node ID.
Note: For networked drives, it is advisable to reserve ID 1 for
spare/replacement drives.
1
1…32 Node ID. 1 = 1
49.03 Baud rate Defines the transfer rate of the link. 115.2 kbps
38.4 kbps 38.4 kbit/s. 1
57.6 kbps 57.6 kbit/s. 2
86.4 kbps 86.4 kbit/s. 3
115.2 kbps 115.2 kbit/s. 4
230.4 kbps 230.4 kbit/s. 5
49.04 Communication
loss time
Sets a timeout for control panel (or PC tool) communication. If
a communication break lasts longer than the timeout, the
action specified by parameter 49.05 Communication loss
action is taken.
10.0 s
0.3…3000.0 s Panel/PC tool communication timeout. 10 = 1 s
49.05 Communication
loss action
Selects how the drive reacts to a control panel (or PC tool)
communication break.
Fault
No action No action taken. 0
Fault Drive trips on 7081 Control panel loss.1
Last speed Drive generates an A7EE Panel loss warning and freezes the
speed to the level the drive was operating at. The speed is
determined on the basis of actual speed using 850 ms low-
pass filtering.
WARNING! Make sure that it is safe to continue
operation in case of a communication break.
2
Speed ref safe Drive generates an A7EE Panel loss warning and sets the
speed to the speed defined by parameter 22.41 Speed ref
safe (or 28.41 Frequency ref safe when frequency reference
is being used).
WARNING! Make sure that it is safe to continue
operation in case of a communication break.
3
49.06 Refresh settings Applies the settings of parameters 49.0149.05.
Note: Refreshing may cause a communication break, so
reconnecting the drive may be required.
Done
Done Refresh done or not requested. 0
No. Name/Value Description Def/FbEq16