170 Parameters
12.30 AI2 scaled at AI2
max
Defines the real value that corresponds to the minimum
analog input AI2 value defined by parameter 12.28 AI2 max.
See the drawing at parameter of 12.29 AI2 scaled at AI2 min.
50.000
-32768.000…
32767.000
Real value corresponding to maximum AI2 value. 1 = 1
12.101 AI1 percent value Value of analog input AI1 in percent of AI1 scaling (12.18 AI1
max - 12.17 AI1 min).
-
0.00…100.00% AI1 value 100 = 1%
12.102 AI2 percent value Value of analog input AI2 in percent of AI2 scaling (12.28 AI2
max - 12.27 AI2 min).
-
0.00…100.00% AI2 value 100 = 1%
13
13 Standard AO
Configuration of standard analog outputs.
13.02 AO force selection The source signals of the analog outputs can be overridden
for eg. testing purposes. A forced value parameter is provided
for each analog output, and its value is applied whenever the
corresponding bit in this parameter is 1.
Note: Boot and power cycle reset the force selections
(parameters 13.02 and 13.11).
0000h
0000h…FFFFh Forced values selector for analog outputs AO1 and AO2. 1 = 1
13.11 AO1 actual value Displays the value of AO1 in mA or V.
This parameter is read-only.
-
0.000…22.000 mA /
0.000…11.000 V
Value of AO1. 1 = 1 mA
13.12 AO1 source Selects a signal to be connected to analog output AO1. Output
frequency
Zero None. 0
Motor speed used 01.01 Motor speed used (page 147). 1
Reserved 2
Output frequency 01.06 Output frequency (page 147). 3
Motor current 01.07 Motor current (page 147). 4
Motor current % of
motor nominal
01.08 Motor current % of motor nom (page 147). 5
Motor torque 01.10 Motor torque (page 147). 6
DC voltage 01.11 DC voltage (page 147). 7
Output power 01.14 Output power (page 148). 8
Reserved 9
Speed ref ramp in 23.01 Speed ref ramp input (page 212). 10
Speed ref ramp out 23.02 Speed ref ramp output (page 213). 11
Speed ref used 24.01 Used speed reference (page 217). 12
Reserved 13
No. Name/Value Description Def/FbEq16
Bit Value
0 1 = Force AO1 to value of parameter 13.13 AO1 forced value. (0 = Normal mode)
1 1 = Force AO2 to value of parameter 13.23 AO2 forced value. (0 = Normal mode)
2…15 Reserved
ACS580 FW.book Page 170 Wednesday, September 21, 2016 9:48 PM