182 Parameters
Other [bit] Source selection (see Terms and abbreviations on page 144). -
15.24 DO1 ON delay Defines the activation delay for digital output DO1 when
15.22 DO1 configuration is set to Digital output.
0.0 s
t
On
= 15.24 DO1 ON delay
t
Off
= 15.25 DO1 OFF delay
0.0 3000.0 s Activation delay for DO1. 10 = 1 s
15.25 DO1 OFF delay Defines the deactivation delay for relay output DO1 when
15.22 DO1 configuration is set to Digital output. See
parameter 15.24 DO1 ON delay.
0.0 s
0.0 3000.0 s Deactivation delay for DO1. 10 = 1 s
15.32 Freq out 1 actual
value
Displays the value of frequency output 1 at digital output DO1
when 15.22 DO1 configuration is set to Frequency output.
This parameter is read-only.
-
0 16000 Hz Value of frequency output 1. 1 = 1 Hz
15.33 Freq out 1 source Selects a signal to be connected to digital output DO1 when
15.22 DO1 configuration is set to Frequency output.
Alternatively, sets the output to excitation mode to feed a
constant current to a temperature sensor.
Not selected
Not selected None. 0
Motor speed used 01.01 Motor speed used (page 147). 1
Output frequency 01.06 Output frequency (page 147). 3
Motor current 01.07 Motor current (page 147). 4
Motor torque 01.10 Motor torque (page 147). 6
DC voltage 01.11 DC voltage (page 147). 7
Output power 01.14 Output power (page 148). 8
Speed ref ramp in 23.01 Speed ref ramp input (page 212). 10
Speed ref ramp out 23.02 Speed ref ramp output (page 213). 11
Speed ref used 24.01 Used speed reference (page
217). 12
Torque ref used 26.02 Torque reference used (page 222). 13
Freq ref used 28.02 Frequency ref ramp output (page 226). 14
Reserved 15
Process PID out 40.01 Process PID output actual (page 278). 16
Other Source selection (see Terms and abbreviations on page 144). -
No. Name/Value Description Def/FbEq16
1
0
1
0
t
On
t
Off
t
On
t
Off
Status of selected
source
DO status
Time
ACS580 FW.book Page 182 Wednesday, September 21, 2016 9:48 PM