290 Parameters
41.31 Set 2 deviation
inversion
See parameter 40.31 Set 1 deviation inversion. Not inverted
(Ref - Fbk)
41.32 Set 2 gain See parameter 40.32 Set 1 gain.1.00
41.33 Set 2 integration
time
See parameter 40.33 Set 1 integration time. 60.0 s
41.34 Set 2 derivation
time
See parameter 40.34 Set 1 derivation time. 0.000 s
41.35 Set 2 derivation
filter time
See parameter 40.35 Set 1 derivation filter time. 0.0 s
41.36 Set 2 output min See parameter 40.36 Set 1 output min.0.0
41.37 Set 2 output max See parameter 40.37 Set 1 output max. 100.0
41.38 Set 2 output freeze See parameter 40.38 Set 1 output freeze. Not selected
41.43 Set 2 sleep level See parameter 40.43 Set 1 sleep level.0.0
41.44 Set 2 sleep delay See parameter 40.44 Set 1 sleep delay. 60.0 s
41.45 Set 2 sleep boost
time
See parameter 40.45 Set 1 sleep boost time. 0.0 s
41.46 Set 2 sleep boost
step
See parameter 40.46 Set 1 sleep boost step. 0.0 PID
customer
units
41.47 Set 2 wake-up
deviation
See parameter 40.47 Set 1 wake-up deviation.0.00 PID
customer
units
41.48 Set 2 wake-up
delay
See parameter 40.48 Set 1 wake-up delay.0.50 s
41.49 Set 2 tracking mode See parameter 40.49
Set 1 tracking mode. Not selected
41.50 Set 2 tracking ref
selection
See parameter 40.50 Set 1 tracking ref selection. Not selected
41.58 Set 2 increase
prevention
See parameter 40.58 Set 1 increase prevention. No
41.59 Set 2 decrease
prevention
See parameter 40.59 Set 1 decrease prevention. No
43
43 Brake chopper
Settings for the internal brake chopper.
43.01 Braking resistor
temperature
Displays the estimated temperature of the brake resistor, or
how close the brake resistor is to being too hot.
The value is given in percent where 100% is the eventual
temperature the resistor would reach when loaded long
enough with its rated maximum load capacity (43.09 Brake
resistor Pmax cont).
The temperature calculation is based on the values of
parameters 43.08, 43.09 and 43.10, and on the assumption
that the resistor is installed as instructed by the manufacturer
(ie it cools down as expected).
This parameter is read-only.
-
0.0…120.0% Estimated brake resistor temperature. 1 = 1%
No. Name/Value Description Def/FbEq16
ACS580 FW.book Page 290 Wednesday, September 21, 2016 9:48 PM