Parameters 315
Setpoint data
storage
Parameter 40.92 Setpoint data storage.41
Other Source selection (see Terms and abbreviations on page 144). -
58.102 Data I/O 2 Defines the address in the drive which the Modbus master
accesses when it reads from or writes to register address
400002.
For the selections, see parameter 58.101 Data I/O 1.
Ref1 16bit
58.103 Data I/O 3 Defines the address in the drive which the Modbus master
accesses when it reads from or writes to register address
400003.
For the selections, see parameter 58.101 Data I/O 1.
Ref2 16bit
58.104 Data I/O 4 Defines the address in the drive which the Modbus master
accesses when it reads from or writes to register address
400004.
For the selections, see parameter 58.101 Data I/O 1.
SW 16bit
58.105 Data I/O 5 Defines the address in the drive which the Modbus master
accesses when it reads from or writes to register address
400005.
For the selections, see parameter 58.101 Data I/O 1.
Act1 16bit
58.106 Data I/O 6 Defines the address in the drive which the Modbus master
accesses when it reads from or writes to register address
400006.
For the selections, see parameter 58.101 Data I/O 1.
Act2 16bit
58.107 Data I/O 7 Parameter selector for Modbus register address 400007.
For the selections, see parameter 58.101 Data I/O 1.
None
…… … …
58.114 Data I/O 14 Parameter selector for Modbus register address 400014.
For the selections, see parameter 58.101 Data I/O 1.
None
71
71 External PID1
Configuration of external PID.
71.01 External PID act
value
See parameter 40.01 Process PID output actual.-
71.02 Feedback act value See parameter 40.02 Process PID feedback actual.-
71.03 Setpoint act value See parameter 40.03 Process PID setpoint actual.-
71.04 Deviation act value See parameter 40.04 Process PID deviation actual.-
No. Name/Value Description Def/FbEq16
ACS580 FW.book Page 315 Wednesday, September 21, 2016 9:48 PM