Parameters 255
32.61 Supervision 6
hysteresis
Defines the hysteresis for the signal monitored by signal
supervision 6.
0.00
0.00…100000.00 Hysteresis. -
34
34 Timed functions
Configuration of the timed functions.
See also section Motor control (page 110).
34.01 Timed functions
status
Status of the combined timers. The status of a combined
timer is the logical OR of all timers connected to it.
This parameter is read-only.
-
0000h…0FFFFh Status of combined timers 1…3. 1 = 1
34.02 Timer status Status of timers 1…12.
This parameter is read-only.
-
0000h…FFFFh Timer status. 1 = 1
No. Name/Value Description Def/FbEq16
Bit Name Description
0 Timed function 1 1 = Active.
1 Timed function 2 1 = Active.
2 Timed function 3 1 = Active.
3…15 Reserved
Bit Name Description
0 Timer 1 1 = Active.
1 Timer 2 1 = Active.
2 Timer 3 1 = Active.
3 Timer 4 1 = Active.
4 Timer 5 1 = Active.
5 Timer 6 1 = Active.
6 Timer 7 1 = Active.
7 Timer 8 1 = Active.
8 Timer 9 1 = Active.
9 Timer 10 1 = Active.
10 Timer 11 1 = Active.
11 Timer 12 1 = Active.
12…15 Reserved
ACS580 FW.book Page 255 Wednesday, September 21, 2016 9:48 PM