294 Parameters
45
45 Energy efficiency
Settings for the energy saving calculators.
See also section Energy saving calculators (page 135).
45.01 Saved GW hours Energy saved in GWh compared to direct-on-line motor
connection. This parameter is incremented when 45.02
Saved MW hours rolls over.
This parameter is read-only (see parameter 45.21 Energy
calculations reset).
-
0…65535 GWh Energy savings in GWh. 1 = 1 GWh
45.02 Saved MW hours Energy saved in MWh compared to direct-on-line motor
connection. This parameter is incremented when 45.03
Saved kW hours rolls over.
When this parameter rolls over, parameter 45.01 Saved GW
hours is incremented.
This parameter is read-only (see parameter 45.21 Energy
calculations reset).
-
0…999 MWh Energy savings in MWh. 1 = 1 MWh
45.03 Saved kW hours Energy saved in kWh compared to direct-on-line motor
connection.
If the internal brake chopper of the drive is enabled, all energy
fed by the motor to the drive is assumed to be converted into
heat, but the calculation still records savings made by
controlling the speed. If the chopper is disabled, then
regenerated energy from the motor is also recorded here.
When this parameter rolls over, parameter 45.02 Saved MW
hours is incremented.
This parameter is read-only (see parameter 45.21 Energy
calculations reset).
-
0.0…999.9 kWh Energy savings in kWh. 10 = 1 kWh
45.04 Saved energy Energy saved in kWh compared to direct-on-line motor
connection.
If the internal brake chopper of the drive is enabled, all energy
fed by the motor to the drive is assumed to be converted into
heat.
This parameter is read-only (see parameter 45.21 Energy
calculations reset).
-
0.0…214748364.0
kWh
Energy savings in kWh. 1 = 1 kWh
45.05 Saved money
x1000
Monetary savings in thousands compared to direct-on-line
motor connection. This parameter is incremented when 45.06
Saved money rolls over.
Specify the currency as text in Main menu - Primary
settings - Clock, region display - Units - Currency.
This parameter is read-only (see parameter 45.21 Energy
calculations reset).
-
0…4294967295
thousands
Monetary savings in thousands of units. 1 = 1 unit