Parameters 283
Timed function 1 Bit 0 of 34.01 Timed functions status (see page 255). 18
Timed function 2 Bit 1 of 34.01 Timed functions status (see page 255). 19
Timed function 3 Bit 2 of 34.01 Timed functions status (see page 255). 20
Supervision 1 Bit 0 of 32.01 Supervision status (see page 248). 21
Supervision 2 Bit 1 of 32.01 Supervision status (see page 248). 22
Supervision 3 Bit 2 of 32.01 Supervision status (see page 248). 23
Other [bit] Source selection (see Terms and abbreviations on page 144). -
40.21 Set 1 internal
setpoint 1
Internal process setpoint 1. See parameter 40.19 Set 1
internal setpoint sel1.
0.00 PID
customer
units
-32768.00…
32767.00 PID
customer units
Internal process setpoint 1. 1 = 1 PID
customer unit
40.22 Set 1 internal
setpoint 2
Internal process setpoint 2. See parameter 40.19 Set 1
internal setpoint sel1.
0.00 PID
customer
units
-32768.00…
32767.00 PID
customer units
Internal process setpoint 2. 1 = 1 PID
customer unit
40.23 Set 1 internal
setpoint 3
Internal process setpoint 3. See parameter 40.19 Set 1
internal setpoint sel1.
0.00 PID
customer
units
-32768.00…
32767.00 PID
customer units
Internal process setpoint 3. 1 = 1 PID
customer unit
40.26 Set 1 setpoint min Defines a minimum limit for the process PID controller
setpoint.
0.00
-32768.00…
32767.00
Minimum limit for process PID controller setpoint. 1 = 1
40.27 Set 1 setpoint max Defines a maximum limit for the process PID controller
setpoint.
32767.00
-32768.00…
32767.00
Maximum limit for process PID controller setpoint. 1 = 1
40.28 Set 1 setpoint
increase time
Defines the minimum time it takes for the setpoint to increase
from 0% to 100%.
0.0 s
0.0…1800.0 s Setpoint increase time. 1 = 1
40.29 Set 1 setpoint
decrease time
Defines the minimum time it takes for the setpoint to decrease
from 100% to 0%.
0.0 s
0.0…1800.0 s Setpoint decrease time. 1 = 1
40.30 Set 1 setpoint
freeze enable
Freezes, or defines a source that can be used to freeze, the
setpoint of the process PID controller. This feature is useful
when the reference is based on a process feedback
connected to an analog input, and the sensor must be
serviced without stopping the process.
1 = Process PID controller setpoint frozen
See also parameter 40.38 Set 1 output freeze.
Not selected
Not selected Process PID controller setpoint not frozen. 0
Selected Process PID controller setpoint frozen. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
No. Name/Value Description Def/FbEq16
ACS580 FW.book Page 283 Wednesday, September 21, 2016 9:48 PM