EasyManua.ls Logo

ABB ACS580 - Page 166

ABB ACS580
462 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
162 Parameters
Timed function 3 Bit 2 of 34.01 Timed functions status (see page 255). 29
Reserved 30…32
Supervision 1 Bit 0 of 32.01 Supervision status (see page 248). 33
Supervision 2 Bit 1 of 32.01 Supervision status (see page 248). 34
Supervision 3 Bit 2 of 32.01 Supervision status (see page 248). 35
Reserved 36…38
Start delay Bit 13 of 06.17 Drive status word 2 (see page 155). 39
RO/DIO control
word bit0
Bit 0 of 10.99 RO/DIO control word (see page 164). 40
RO/DIO control
word bit1
Bit 1 of 10.99 RO/DIO control word (see page 164). 41
RO/DIO control
word bit2
Bit 2 of 10.99 RO/DIO control word (see page 164). 42
Reserved 43…44
PFC1 Bit 0 of 76.01 PFC status (see page 318). 45
PFC2 Bit 1 of 76.01 PFC status (see page 318). 46
PFC3 Bit 2 of 76.01 PFC status (see page 318). 47
PFC4 Bit 3 of 76.01 PFC status (see page 318). 48
Other [bit] Source selection (see Terms and abbreviations on page 144
). -
10.25 RO1 ON delay Defines the activation delay for relay output RO1. 0.0 s
t
On
= 10.25 RO1 ON delay
t
Off
= 10.26 RO1 OFF delay
0.0 3000.0 s Activation delay for RO1. 10 = 1 s
10.26 RO1 OFF delay Defines the deactivation delay for relay output RO1. See
parameter 10.25 RO1 ON delay.
0.0 s
0.0 3000.0 s Deactivation delay for RO1. 10 = 1 s
10.27 RO2 source Selects a drive signal to be connected to relay output RO2.
For the available selections, see parameter 10.24 RO1
source.
Running
No. Name/Value Description Def/FbEq16
1
0
1
0
t
On
t
Off
t
On
t
Off
Status of selected
source
RO status
Time
ACS580 FW.book Page 162 Wednesday, September 21, 2016 9:48 PM

Table of Contents

Other manuals for ABB ACS580

Related product manuals