214 Parameters
23.14 Acceleration time 2 Defines acceleration time 2. See parameter 23.12
Acceleration time 1.
60.000 s
0.000…1800.000 s Acceleration time 2. 10 = 1 s
23.15 Deceleration time 2 Defines deceleration time 2. See parameter 23.13
Deceleration time 1.
60.000 s
0.000…1800.000 s Deceleration time 2. 10 = 1 s
23.20 Acc time jogging Defines the acceleration time for the jogging function ie. the
time required for the speed to change from zero to the speed
value defined by parameter 46.01 Speed scaling.
See section Jogging (page 118).
60.000 s
0.000…1800.000 s Acceleration time for jogging. 10 = 1 s
23.21 Dec time jogging Defines the deceleration time for the jogging function ie. the
time required for the speed to change from the speed value
defined by parameter 46.01 Speed scaling to zero.
See section Jogging (page 118).
60.000 s
0.000…1800.000 s Deceleration time for jogging. 10 = 1 s
23.23 Emergency stop
time
Defines the time inside which the drive is stopped if an
emergency stop Off3 is activated (ie. the time required for the
speed to change from the speed value defined by parameter
46.01 Speed scaling or 46.02 Frequency scaling to zero).
Emergency stop mode and activation source are selected by
parameters 21.04 Emergency stop mode and 21.05
Emergency stop source respectively. Emergency stop can
also be activated through fieldbus.
Note:
Emergency stop Off1 uses the standard deceleration ramp
as defined by parameters 23.1123.15.
The same parameter value is also used in frequency
control mode (ramp parameters 28.71…).
3.000 s
0.000…1800.000 s Emergency stop Off3 deceleration time. 10 = 1 s
No. Name/Value Description Def/FbEq16
ACS580 FW.book Page 214 Wednesday, September 21, 2016 9:48 PM