Parameters 191
20.09 Ext2 in2 source Selects source 2 for parameter 20.06 Ext2 commands.
For the available selections, see parameter 20.03 Ext1 in1
source.
Not selected
20.10 Ext2 in3 source Selects source 3 for parameter 20.06 Ext2 commands.
For the available selections, see parameter 20.03 Ext1 in1
source.
Not selected
20.11 Run enable stop
mode
Selects the way the motor is stopped when the run enable
signal switches off.
The source of the run enable signal is selected by parameter
20.12 Run enable 1 source.
Coast
Coast Stop by switching off the output semiconductors of the drive.
The motor coasts to a stop.
WARNING! If a mechanical brake is used, ensure it is
safe to stop the drive by coasting.
0
Ramp Stop along the active deceleration ramp. See parameter
group 23 Speed reference ramp on page 212.
1
Torque limit Stop according to torque limits (parameters 30.19 and 30.20). 2
20.12 Run enable 1
source
Selects the source of the external run enable signal. If the run
enable signal is switched off, the drive will not start. If already
running, the drive will stop according to the setting of
parameter 20.11 Run enable stop mode.
1 = Run enable signal on.
Note: This parameter cannot be changed while the drive is
running.
See also parameter 20.19 Enable start command.
Selected
Not selected 0. 0
Selected 1. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02
DI delayed status, bit 5). 7
Reserved 8…17
Timed function 1 Bit 0 of 34.01 Timed functions status (see page 255). 18
Timed function 2 Bit 1 of 34.01 Timed functions status (see page 255). 19
Timed function 3 Bit 2 of 34.01 Timed functions status (see page 255). 20
Reserved 21…23
Supervision 1 Bit 0 of 32.01 Supervision status (see page 248). 24
Supervision 2 Bit 1 of 32.01 Supervision status (see page 248). 25
Supervision 3 Bit 2 of 32.01 Supervision status (see page 248). 26
Reserved 27…29
FBA A MCW bit 3 Control word bit 3 received through fieldbus interface A. 30
EFB MCW bit 3 Control word bit 3 received through the embedded fieldbus
interface.
31
Other [bit] Source selection (see Terms and abbreviations on page 144). -
No. Name/Value Description Def/FbEq16
ACS580 FW.book Page 191 Wednesday, September 21, 2016 9:48 PM