328 Parameters
ABB standard
(vector)
ABB standard (vector) macro (see page 62). For vector motor
control.
17
96.05 Macro active Shows which control macro is currently selected. See chapter
Control macros (page 59) for more information.
To change the macro, use parameter 96.04 Macro select.
ABB
standard
ABB standard Factory macro (see page 60). For scalar motor control. 1
Hand/Auto Hand/Auto macro (see page 70). 2
Hand/PID Hand/PID macro (see page 72). 3
3-wire 3-wire macro see page 60). 11
Alternate Alternate macro see page 66). 12
Motor
potentiometer
Motor potentiometer macro (see page 68). 13
PID PID macro (see page 74). 14
Panel PID Panel PID macro (see page 76). 15
PFC PFC macro (see page 78). 16
ABB standard
(vector)
ABB standard (vector) macro (see page 61). For vector motor
control.
17
96.06 Parameter restore Restores the original settings of the control program, ie.
parameter default values.
Note: This parameter cannot be changed while the drive is
running.
Done
Done Restoring is completed. 0
Restore defaults Restores all editable parameter values to default values,
except
• motor data and ID run results
• I/O extension module settings
• end user texts, such as customized warnings and faults,
and the drive name
• control panel/PC communication settings
• fieldbus adapter settings
• control macro selection and the parameter defaults
implemented by it
• parameter 95.20 HW options word 1 and the differentiated
defaults implemented by it.
8
Clear all Restores all editable parameter values to default values,
except
• end user texts, such as customized warnings and faults,
and the drive name
• control macro selection and the parameter defaults
implemented by it
• parameter 95.20 HW options word 1 and the differentiated
defaults implemented by it
•group 49 Panel port communication parameters.
62
Reset all fieldbus
settings
Restores all fieldbus and communication related settings to
default values.
Note:
Fieldbus, control panel and PC tool communication are
interrupted during the restore.
32
Reset home view Restores the home view layout back to show the values of the
default parameters defined by the control macro in use
512
Reset end user
texts
Restores all end user texts to default values, including the
drive name, contact info, customized fault and warning texts,
PID unit and currency unit.
1024
No. Name/Value Description Def/FbEq16