Control macros 61
Terminal sizes:
R0…R5: 0.2…2.5 mm
2
(terminals +24V, DGND, DCOM, B+, A-)
0.14…1.5 mm
2
(terminals DI, AI, AO, AGND, RO, STO)
R6…R9: 0.14…2.5 mm
2
(all terminals)
Tightening torques: 0.5…0.6 N·m (0.4 lbf·ft)
Notes:
1)
See Menu - Primary settings - Start, stop, reference - Constant frequencies or parameter
group 28 Frequency reference chain.
2)
See Menu - Primary settings - Ramps or parameter group 28 Frequency reference chain.
3)
Ground the outer shield of the cable 360 degrees under the grounding clamp on the
grounding shelf for the control cables.
4)
Connected with jumpers at the factory.
5)
Only frames R6…R11 have terminals 40 and 41 for external 24 V AC/DC input.
6)
All control boards do not have switches S1, S2 and S3. In that case, select voltage or current
for inputs AI1 and AI2 and output AO1 with parameters 12.15, 12.25 and 13.15, respectively.
Input signals
• Analog frequency reference (AI1)
• Start/stop selection (DI1)
• Direction selection (DI2)
• Constant frequency selection (DI3, DI4)
• Ramp set (1 of 2) selection (DI5)
Output signals
• Analog output AO1: Output frequency
• Analog output AO2: Motor current
• Relay output 1: Ready run
• Relay output 2: Running
• Relay output 3: Fault (-1)
DI3 DI4 Operation/Parameter
0 0 Set frequency through AI1
1028.26 Constant frequency 1
0128.27 Constant frequency 2
1128.28 Constant frequency 3
DI5 Ramp set Parameters
01 28.72 Freq acceleration time 1
28.73 Freq deceleration time 1
12 28.74 Freq acceleration time 2
Freq deceleration time 2
ACS580 FW.book Page 61 Wednesday, September 21, 2016 9:48 PM