Parameters 329
Reset motor data Restores all motor nominal values and motor ID run results to
default values.
2
All to factory
defaults
Restores all drive parameters and settings back to initial
factory values, except
parameter 95.20 HW options word 1 and the differentiated
defaults implemented by it.
34560
96.07 Parameter save
manually
Saves the valid parameter values to the permanent memory
on the drive control unit to ensure that operation can continue
after cycling the power. Save the parameters with this
parameter
to store values sent from the fieldbus
when using external +24 V DC power supply to the control
unit: to save parameter changes before you power down
the control unit. The supply has a very short hold-up time
when powered off.
Note: A new parameter value is saved automatically when
changed from the PC tool or control panel but not when
altered through a fieldbus adapter connection.
Done
Done Save completed. 0
Save Save in progress. 1
96.08 Control board boot Changing the value of this parameter to 1 reboots the control
unit (without requiring a power off/on cycle of the complete
drive module).
The value reverts to 0 automatically.
No action
No action 1 = No action. 0
Reboot 1 = Reboot the control unit. 1
96.10 User set status Shows the status of the user parameter sets.
This parameter is read-only.
See also section User parameter sets (page 139).
-
n/a No user parameter sets have been saved. 0
Loading A user set is being loaded. 1
Saving A user set is being saved. 2
Faulted Invalid or empty parameter set. 3
User1 IO active User set 1 has been selected by parameters 96.12 User set
I/O mode in1 and 96.13 User set I/O mode in2.
4
User2 IO active User set 2 has been selected by parameters 96.12 User set
I/O mode in1 and 96.13 User set I/O mode in2.
5
User3 IO active User set 3 has been selected by parameters 96.12 User set
I/O mode in1 and 96.13 User set I/O mode in2.
6
User4 IO active User set 4 has been selected by parameters 96.12 User set
I/O mode in1 and 96.13 User set I/O mode in2.
7
Reserved 8…19
User1 backup User set 1 has been saved or loaded. 20
User2 backup User set 2 has been saved or loaded. 21
User3 backup User set 3 has been saved or loaded. 22
User4 backup User set 4 has been saved or loaded. 23
No. Name/Value Description Def/FbEq16
ACS580 FW.book Page 329 Wednesday, September 21, 2016 9:48 PM