Control macros 71
Terminal sizes:
R0…R5: 0.2…2.5 mm
2
(terminals +24V, DGND, DCOM, B+, A-)
0.14…1.5 mm
2
(terminals DI, AI, AO, AGND, RO, STO)
R6…R9: 0.14…2.5 mm
2
(all terminals)
Tightening torques: 0.5…0.6 N·m (0.4 lbf·ft)
Notes:
1)
The signal source is powered externally. See the manufacturer’s instructions. To use sensors
supplied by the drive aux. voltage output, see chapter Electrical installation, section
Connection examples of two-wire and three-wire sensors in the Hardware manual of the
drive.
2)
Ground the outer shield of the cable 360 degrees under the grounding clamp on the
grounding shelf for the control cables.
3)
Connected with jumpers at the factory.
4)
Only frames R6R11 have terminals 40 and 41 for external 24 V AC/DC input.
5)
All control boards do not have switches S1, S2 and S3. In that case, select voltage or current
for inputs AI1 and AI2 and output AO1 with parameters 12.15, 12.25 and 13.15, respectively.
Input signals
Two speed/frequency analog reference (AI1, AI2)
Control location (Hand or Auto) selection (DI3)
Start/stop selection, Hand (DI1)
Direction selection, Hand (DI2)
Start/stop selection, Auto (DI6)
Direction selection, Auto (DI5)
Run enable (DI4)
Output signals
Analog output AO1: Output frequency
Analog output AO2: Motor current
Relay output 1: Ready run
Relay output 2: Running
Relay output 3: Fault (-1)