The following figure illustrates the cable routing guidelines with an example drive.
min. 300 mm (12 in)
min. 300 mm (12 in)
min. 500 mm (20 in)
min. 500 mm (20 in)
min. 200 mm (8 in)
90°
1
2 4
4
3
2
1
3
2
3
Motor cable1
Input power cable2
Control cable3
Brake resistor or chopper cable (if any)4
Continuous motor cable shield/conduit and metal enclosure for
equipment on the motor cable
To minimize the emission level when safety switches, contactors, connection boxes
or similar equipment are installed on the motor cable between the drive and the motor:
Install the equipment in a metal enclosure.
Use either a symmetrical shielded cable, or install the cabling in a metal conduit.
Make sure that there is a good and continuous galvanic connection in the
shield/conduit between drive and motor.
Connect the shield/conduit to the protective ground terminal of the drive and the
motor.
Separate control cable ducts
Put 24 V DC and 230 V AC (120 V AC) control cables in separate ducts, unless the 24 V DC
cable is insulated for 230 V AC (120 V AC) or insulated with an insulation sleeving for
230 V AC (120 V AC).
24 V DC
230 V AC
(120 V AC)
230 V AC
(120 V AC)
24 V DC
106 Guidelines for planning the electrical installation