Dimensions and weights
See chapter Dimensions (page 251)
Free space requirements
The values are as required by cooling, maintenance and/or operation of the pressure
relief (if present). Also obey the general mechanical installation instructions.
AboveSidesFront
in.mmin.mmin.mm
15.75
400
Measured from
the base plate of
the cabinet top.
00591500
Losses, cooling data and noise
Noise
Typical power loss
1)
Air flow
ACS880-07-…
dB(A)Wft
3
/minm
3
/h
U
N
= 400 V, 6-pulse connection
7318751252542901140A-3
7420218336757201250A-3
7423917336757201480A-3
7431105336757201760A-3
7636468505085802210A-3
7646360505085802610A-3
U
N
= 400 V, 12-pulse connection
7316344336757200990A-3+A004
7418095336757201140A-3+A004
7420451336757201250A-3+A004
7424270336757201480A-3+A004
7431067336757201760A-3+A004
76363225892100102210A-3+A004
76466465892100102610A-3+A004
U
N
= 500 V, 6-pulse connection
7317883252542901070A-5
7421491336757201320A-5
7424164336757201450A-5
7427245336757201580A-5
7529899420871501800A-5
7533138420871501980A-5
U
N
= 500 V, 12-pulse connection
7316901336757200990A-5+A004
232 Technical data