Air inlet area1
Support the plinth of the cabinet all round.
The air duct must be able to supply a sufficient volume of cooling air. See technical
data for the minimum air flow values.
Top cable entry adapter and joining cubicles have no air inlet.
WARNING!
Make sure that the incoming air is sufficiently clean. If not, dust goes into the
cabinet. The outlet filter on the cabinet roof prevents dust from going out. The
collected dust can cause drive malfunction and danger of fire.
■
Air outlet duct on the cabinet roof (option +C130)
The option adds air outlet ducts to each cubicle of the cabinet line-up. The outlet
diameter (and quantity) of the ducts depend on the cubicle width. The ducts used are
from the Veloduct series by FläktGroup.
ChannelOutlet duct
Cubicle width
(mm)
Recommended
inner diameter
(mm)
Cross-sectional
area (m
2
)
Inner diameter
(mm)
Outer diameter
(mm)
Veloduct type
200.0 … 200.70.030194200BDEA-6-020300
315.0 … 315.90.073304310BDEA-6-031400
315.0 … 315.90.073304310BDEA-6-031500
400.0 … 401.00.122394400BDEA-6-040600
400.0 … 401.00.122394400BDEA-6-040700
315.0 … 315.90.1453043102 × BDEA-6-031800
315.0 … 315.90.1453043102 × BDEA-6-0311000
The ventilation system must keep the static pressure in the air outlet duct sufficiently
below the pressure of the room where the drive is located in order that the cabinet
fans can produce the required air flow through the cabinet. Make sure that no dirty
Mechanical installation 83