Examining the installation site
Examine the installation site. Make sure that:
The installation site is sufficiently ventilated or cooled to remove heat from the
drive. See the technical data.
The ambient conditions of the drive meet the specifications. See the technical
data.
The material behind, above and below the drive is non-flammable.
There is sufficient free space above the drive for cooling, maintenance, and
operation of the pressure relief (if present).
The floor that the drive cabinet is installed on is of non-flammable material, as
smooth as possible, and strong enough to support the weight of the unit. Check
the floor flatness with a spirit level. The maximum allowed deviation from the
surface level is 5 mm (0.2 in) in every 3 meters (10 ft). Level the installation site, if
necessary, as the cabinet is not equipped with adjustable feet.
Do not install the drive on an elevated platform or a recess. The module
extraction/installation ramp included with the drive is only suitable for a height
difference of 50 mm (2 in) maximum (ie. the standard plinth height of the drive).
Necessary tools
The tools required for moving the unit to its final position, fastening it to the floor
and wall and tightening the connections are listed below:
crane, fork-lift or pallet truck (check load capacity!), slate/spud bar, jack and rollers
Pozidriv and Torx screwdrivers
torque wrench
set of wrenches or sockets.
Examining the delivery
The drive delivery contains:
68 Mechanical installation