Motor connection data
Asynchronous AC induction motors, permanent magnet synchronous motors
and AC induction servomotors, ABB synchronous reluctance (SynRM) motors
Motor types
0 …
U
1
, 3-phase symmetrical,
U
max
at the field weakening pointVoltage (
U
2
)
0…500 Hz (0…120 Hz with sine output filters (option +E206))Frequency (
f
2
)
• For higher operational output frequencies, please contact your local ABB
representative.
• Operation above 150 Hz may require type-specific derating. For more in-
formation, contact your local ABB representative.
See the rating tables.Current
3 kHz (typical). The switching frequency can vary per frame and voltage. For
exact values, contact your local ABB representative.
Switching frequency
500 m (1640 ft).Maximum recommended
motor cable length
Note: Longer cables cause a motor voltage decrease which limits the available
motor power. The decrease depends on the motor cable length and character-
istics. Contact ABB for more information. Also note that a sine filter (optional)
at the drive output also causes a voltage decrease.
Note: With motor cables longer than 150 m (492 ft) the EMC Directive require-
ments may not be fulfilled.
Efficiency
97 … 98% at nominal power level depending on drive type.
The efficiency is not calculated according to the ecodesign standard IEC 61800-9-2.
Energy efficiency data (ecodesign)
Energy efficiency data according to IEC-61800-9-2 is available from
https://ecodesign.drivesmotors.abb.com and from ACS880-07 drives (560 to 2800
kW) energy efficiency data (EU ecodesign) supplement (3AXD50000788231 [English]).
Protection classes
IP22 (standard), IP42 (option +B054), IP54 (option +B055)Degrees of protection
(IEC/EN 60529)
UL Type 1 (standard), UL Type 1 (option +B054), UL Type 12 (option +B055).
For indoor use only.
Enclosure types (UL50)
B – ASSEMBLY providing personnel and ASSEMBLY protection under arcing
conditions.
Tested at the following voltage with an arcing current of 65 kA for 300 milli-
seconds:
Arcing class
(IEC TR 61641)
• 400 V units (indicated by "-3" in drive type): 420 V
• 500 V units (indicated by "-5" in drive type): 550 V
• 690 V units (indicated by "-7" in drive type): 760 V
III, except for auxiliary power connections (fan, control, heating, lighting etc)
which are category II.
Overvoltage category
(IEC/EN 60664-1)
IProtective class
(IEC/EN 61800-5-1)
238 Technical data