Electrical installation of custom brake resistors
Connection diagram
R+ R-
R+ R-
1 2 3
t°
1 2
X1
Brake chopper cubicle
Brake resistor cubicle
Connection procedure
WARNING!
Obey the instructions in chapter Safety instructions. If you ignore them,
injury or death, or damage to the equipment can occur.
Do the steps in section Electrical safety precautions in chapter Safety instructions
before you start the work.
Connect the resistor cable at the resistor end only. If a shielded three-conductor
cable is used, cut off the third conductor. Ground the twisted shield of the cable
as well as any separate PE conductor (if present).
At the chopper end of the cable, connect the R+ and R- conductors of the resistor
cable together. Measure the insulation resistance between the combined
conductors and the PE conductor by using a measuring voltage of 1 kV DC. The
insulation resistance must be higher than 1 Mohm.
340 Resistor braking