4. Dispose of the old battery according to local disposal rules or applicable laws.
5. Set the real-time clock.
UCU control unit types
Different variants of the UCU control units are used in ACS880 drives: UCU-22…24.
These have a different number of converter module connections but are otherwise
identical. The UCU types are interchangeable as long as the number of connections
is sufficient. For example, the UCU-24 can be used as a direct replacement for both
UCU-22 and UCU-23.
Replacing the memory unit (UCU-22…24)
WARNING!
Obey the safety instructions of the drive. If you ignore them, injury or
death, or damage to the equipment can occur. If you are not a qualified
electrical professional, do not do installation, commissioning or
maintenance work.
After replacing a control unit, you can keep the existing parameter settings by
transferring the memory unit from the defective control unit to the new control unit.
WARNING!
Do not remove or install the memory unit when the control unit is powered.
1. Stop the drive and do the steps in section Electrical safety precautions (page 21)
before you start the work.
2. Make sure that the control unit is not powered.
3. Push and hold in the clips on the memory unit. Pull the memory unit out.
4. Push the new memory unit in.
218 Maintenance