Connecting a motor temperature sensor to the drive through an
option module
This table shows:
• option module types that you can use for the motor temperature sensor connection
• insulation or isolation level that each option module forms between its temperature
sensor connector and other connectors
• temperature sensor types that you can connect to each option module
• temperature sensor insulation requirement in order to form, together with the
insulation of the option module, a reinforced insulation between the motor live
parts and the drive control unit.
Temperature sensor in-
sulation requirement
Temperature sensor typeOption module
Pt100,
Pt1000
KTYPTCInsulation/IsolationType
Reinforced insulationxxxGalvanic isolation between sensor
connector and drive control unit
connector. No isolation between
sensor connector and other I/O
connectors.
FIO-11
Reinforced insulation--xGalvanic isolation between sensor
connector and drive control unit
connector. No isolation between
sensor connector and TTL encoder
emulation output.
FEN-01
Reinforced insulation-xxGalvanic isolation between sensor
connector and drive control unit
connector. No isolation between
sensor connector and TTL encoder
emulation output.
FEN-11
Reinforced insulation-xxGalvanic isolation between sensor
connector and drive control unit
connector. No isolation between
sensor connector and TTL encoder
emulation output.
FEN-21
Reinforced insulation-xxGalvanic isolation between sensor
connector and drive control unit
connector. No isolation between
sensor connector and other connect-
ors.
FEN-31
Reinforced or basic insu-
lation. With basic insula-
tion, the other I/O con-
nectors of the option
module must be kept
disconnected.
xxxBasic insulation between sensor
connector and drive control unit
connector. No insulation between
sensor connector and other I/O
connectors.
FAIO-01
No special requirement--xReinforced insulation between
sensor connector and other connect-
ors (including drive control unit
connector).
FPTC-
01/02
1)
1)
Suitable for use in safety functions (SIL2 / PL c classified).
114 Guidelines for planning the electrical installation