Connecting a motor temperature sensor to the drive through an
option module
This table shows:
option module types that you can use for the motor temperature sensor connection
insulation or isolation level that each option module forms between its temperature
sensor connector and other connectors
temperature sensor types that you can connect to each option module
temperature sensor insulation requirement in order to form, together with the
insulation of the option module, a reinforced insulation between the motor live
parts and the drive control unit.
Temperature sensor in-
sulation requirement
Temperature sensor typeOption module
Pt100,
Pt1000
KTYPTCInsulation/IsolationType
Reinforced insulationxxxGalvanic isolation between sensor
connector and drive control unit
connector. No isolation between
sensor connector and other I/O
connectors.
FIO-11
Reinforced insulation--xGalvanic isolation between sensor
connector and drive control unit
connector. No isolation between
sensor connector and TTL encoder
emulation output.
FEN-01
Reinforced insulation-xxGalvanic isolation between sensor
connector and drive control unit
connector. No isolation between
sensor connector and TTL encoder
emulation output.
FEN-11
Reinforced insulation-xxGalvanic isolation between sensor
connector and drive control unit
connector. No isolation between
sensor connector and TTL encoder
emulation output.
FEN-21
Reinforced insulation-xxGalvanic isolation between sensor
connector and drive control unit
connector. No isolation between
sensor connector and other connect-
ors.
FEN-31
Reinforced or basic insu-
lation. With basic insula-
tion, the other I/O con-
nectors of the option
module must be kept
disconnected.
xxxBasic insulation between sensor
connector and drive control unit
connector. No insulation between
sensor connector and other I/O
connectors.
FAIO-01
No special requirement--xReinforced insulation between
sensor connector and other connect-
ors (including drive control unit
connector).
FPTC-
01/02
1)
1)
Suitable for use in safety functions (SIL2 / PL c classified).