Single-channel connection of activation switch (BCU-x2)
+24 V
OUT
SGND
IN2
K
IN1
1
2
Note:
Both STO inputs (IN1, IN2) must be connected to the activation switch. Otherwise, no SIL/PL classi-
fication is given.
Pay special attention to avoiding any potential failure modes for the wiring. For example, use shielded
cable. For measures for fault exclusion of wiring, see eg. EN ISO 13849-2:2012, table D.4.
Drive1
Control unit2
Activation switch
Note: A single-channel activation switch can limit the SIL/PL capability of the safety function
to a lower level than the SIL/PL capability of the STO function of the drive.
K
Single-channel connection of activation switch (UCU-22…24)
OUT
SGND
STO1
STO2
+24 V
1
2
K
Note:
Both STO inputs (STO1, STO2) must be connected to the activation switch. Otherwise, no SIL/PL
classification is given.
Pay special attention to avoiding any potential failure modes for the wiring. For example, use shielded
cable. For measures for fault exclusion of wiring, see eg. EN ISO 13849-2:2012, table D.4.
Drive1
Control unit2
Activation switch
Note: A single-channel activation switch can limit the SIL/PL capability of the safety function
to a lower level than the SIL/PL capability of the STO function of the drive.
K
312 The Safe torque off function