Requirements for non-ABB motors,
P
n
< 100 kW (134 hp)
See also Abbreviations (page 96).
Requirement forNominal AC line
voltage
Motor type
ABB d
u
/d
t
and common mode filters, insulated
N-end motor bearings
Motor insula-
tion sys-
tem
1)
P
n
< 100 kW and frame size < IEC 315
P
n
< 134 hp and frame size < NEMA 500
-
Û
LL
= 1300 V,
0.2 µs rise
time
U
n
≤ 420 VRandom-woundand
form-wound
+ d
u
/d
tÛ
LL
= 1300 V420 V <
U
n
≤ 500 V
-
Û
LL
= 1600 V,
0.2 µs rise
time
+ d
u
/d
tÛ
LL
= 1600 V500 V <
U
n
≤ 600 V
-
Û
LL
= 1800 V,
0.2 µs rise
time
+ d
u
/d
tÛ
LL
= 1800 V600 V <
U
n
≤ 690 V
-
Û
LL
= 2000 V,
0.3 µs rise
time
1)
These are typical values. The network topology and grounding, drive type, cable type, cable length, and motor type
have an effect on the phase-to-phase and phase-to-ground voltages of the motor. For motor dimensioning and
selection, refer to IEC 60034-18-41, IEC 60034-18-42 and IEC/TC 60034-25. For more information, contact ABB.
Guidelines for planning the electrical installation 95